Capstone Turbine Corporation • 21211 Nordhoff Street • Chatsworth • CA 91311 • USA Application Notes: Fuel Gas Booster Installation Instructions – Model C60 LPNG The Fuel Gas Booster may be supplied with an optional Installation and Maintenance Tool Kit comprised of various tools, including a hand pump and lubricating fluid. These tools, in addition to the Maintenance Parts Kit are used to maintain the Fuel Gas Booster at optimum efficiency. Each site should have at least one Fuel Gas Booster Installation and Maintenance Tool Kit plus one Maintenance Parts Kit. Refer to the Fuel Gas Booster Owner's manual for additional information. Safety Precautions Always adhere to the Safety Precautions listed below when servicing your MicroTurbine and associated equipment: 􏰪 AlwaysobservetheappropriateSafetyPrecautions. 􏰪 Never work on energized equipment. Always check for voltages with the proper test equipment. 􏰪 Before servicing, always check to ensure that your MicroTurbine is disconnected from the utility. 􏰪 If the MicroTurbine is equipped with a battery pack (i.e., Stand Alone option), open the battery isolation switch and unplug the battery cable. 􏰪 Wait at least 10 minutes after shutdown and disconnection before servicing. 􏰪 RefertotheMicroTurbineUser’sManualforSafetyInstructions. Software Setup Program the MicroTurbine software before any electrical connections to the Fuel Gas Booster as follows: 1. Ensure that there are no electrical connections between the MicroTurbine and the Fuel Gas Booster. 2. Power up the MicroTurbine. 3. Program the output relays as follows: Using the control panel on the MicroTurbine, proceed as follows: a. On the UCB Relays menu, Relay #1 submenu, set EXT LOAD to ACTIVE CLOSED. b. On the System Settings menu, Fault Input #1 submenu, set Fault Input #1 to ENABLE (Fault signal from FGB). On Fault Input #1 submenu, set SSL to 3 and time to 12 seconds. 4. Power down the MicroTurbine. 512001-001 Rev C (March 2004) Page 2 of 8 This information is proprietary to Capstone Turbine Corporation. Neither this document nor the information contained herein shall be copied, disclosed to others, or used for any purposes other than the specific purpose for which this document was delivered. Capstone reserves the right to change or modify without notice, the design, the product specifications, and/or the contents of this document without incurring any obligation either with respect to equipment previously sold or in the process of construction. NOTE The Capstone software must be set up to treat the Fuel Gas Booster as an External Auxiliary Load. Any of the output relays may be configured to perform this function; however, the specified wiring connections demonstrate the use of Relay #1.

PDF Image | Fuel Gas Booster Installation Instructions Model C60 MicroTurbine - Low Pressure Natural GasApplication Notes

fuel-gas-booster-installation-instructions-model-c60-microtu-002

PDF Search Title:

Fuel Gas Booster Installation Instructions Model C60 MicroTurbine - Low Pressure Natural GasApplication Notes

Original File Name Searched:

512001_C60_Vertical_FGB_App_Notes.pdf

DIY PDF Search: Google It | Yahoo | Bing

Capstone Turbine and Microturbine: Capstone microturbines used and new surplus for sale listing More Info

Consulting and Strategy Services: Need help with Capstone Turbine, sizing systems, applications, or renewable energy strategy, we are here to assist More Info

Container Lumber Dry Kiln: Since 1991 developing and innovating dry kilns using standard shipping containers More Info

Supercritical CO2 Lumber Dry Kiln: Compact fast drying in 3 days or less for small amounts of wood and lumber drying More Info

BitCoin Mining: Bitcoin Mining and Cryptocurrency... More Info

Publications: Capstone Turbine publications for microturbine and distributed energy More Info

FileMaker Software for Renewable Energy Developing database software for the renewable energy industry More Info

CO2 Gas to Liquids On-Demand Production Cart Developing a supercritical CO2 to alcohol on-demand production system (via Nafion reverse fuel cell) More Info

Stranded Gas for low cost power Bitcoin Mining Using stranded gas for generators may provide breakthrough low power costs for cryptocurrency miners. More Info

CONTACT TEL: 608-238-6001 Email: greg@globalmicroturbine.com | RSS | AMP