Text from PDF Page: 014

Capstone Turbine Corporation • 21211 Nordhoff Street • Chatsworth • CA 91311 • U.S.A. Technical Reference: Display Panel Menu Options - Capstone MicroTurbine Logoff The Logoff submenu on line two reverts the system to base password mode, disabling all password protected parameter adjustments. The user should manually log off using this menu after making any required changes. Modem Power (C60) Turns modem ON or OFF. Time of Use Menu The top-level Time of Use menu is used to program the on/off and power demand schedules for the MicroTurbine based on time and day of week. When Time of Use Grid Connect Dispatching mode is activated, up to 20 events may be programmed. An event consists of an ON or OFF command, a power level demand adjustment, and the time that the event executes. LMTOU Event [Load Management Time Of Use Event] The LMTOU Event submenu on line two displays the event number as 1/20, 2/20, through 20/20, and allows the selection of an event to be configured. The LMTOU Event submenus are detailed below. Day of Week Identifies the day of the week for the event execution. 1 = Sunday, through 7 = Saturday. Entering 0 (zero) disables the event without changing its time or other parameters. Time