Capstone Turbine Corporation • 21211 Nordhoff Street • Chatsworth • CA 91311 • USA Dual Mode System Controller (DMSC): User’s Manual UCB Output Relay Settings Use CRMS to make the necessary settings (refer to Table 8) to the applicable UCB output relay as follows: Any output relay (1-6) can be selected, but the selected number must match the UCB to DMSC connections. 1. Select the number of the UCB output relay that is connected to the DMSC. Refer to the DMSC Technical Reference (410071) for wiring data. 2. Set the selected output relay to ACTIVE CLOSED. 3. Set the selected output relay to DUAL MODE CNTRL. These settings can also be done with an RS-232 command as described in the notes below. NOTE Table 8. UCB Output Relay Parameters UCB Relay