Capstone Turbine Corporation • 21211 Nordhoff Street • Chatsworth • CA 91311 • U.S.A. Technical Reference: Display Panel Menu Options - Capstone MicroTurbine
Flow Spt (Flow Setpoint)
Sets the CHP water flow rate (0 to 80 gallons per minute). Default is 0 Gal/Min.
Overtemp Bypass (Overtemperature Bypass)
Sets the water temperature setpoint at which an Overtemp Fault is declared in Thermal Bypass mode. This value is ignored in Thermal or Electrical Priority modes. As shipped, the factory default is 120 °F. Adjustable range is from 120 to 224 °F.
Overtemp Rcvry (Overtemperature Recovery)
Sets the water temperature setpoint at which an Overtemp Fault is declared in Thermal Priority and Electrical Priority modes. This value is ignored in Thermal Bypass mode. As shipped, the factory default is 120 °F. Adjustable range is from 120 to 224 °F.
CHP Control RTD
User setting that selects the inlet or outlet Resistive Thermal Device (RTD) as the controlling sensor to provide temperature measurement feedback to the Heat Recovery Module (HRM). This setting is overridden if temperature data is received from an external temperature sensor. See the UCB Analog Inputs (C60) section below for configurations.
UCB Analog Inputs (C60)
The top-level UCB Analog Inp (Inputs) menu sets functionality for up to three analog inputs that may be selectively mapped on the User Connection Board (UCB). Each of these inputs may be configured for either current or voltage. Analog input functionality is usually established at installation and not changed. Refer to Model C60 Electrical Technical Reference (410001) for details on UCB Analog Inputs.
Input Number
Selects one of three available analog inputs.
Function