Capstone SERIES 5000 FAULT CODES

PDF Publication Title:

Capstone SERIES 5000 FAULT CODES ( capstone-series-5000-fault-codes )

Previous Page View | Next Page View | Return to Search List

Text from PDF Page: 006

5000 Fault (Cont’d) SPV/GSPV Faults (Cont’d) Bit # SPV FAULT Analysis Repair Solution 25 Control Valve Under Voltage Check Intra Harness Connections at DPC and Device Secure Intra Harness Check Intra Harness Cable for Water or Damage Replace Intra Harness Verify 12V on Intra B Power measured dur- ing start/ No12V replace DPC Control Board Replace DPC Control Board Voltage sensing circuitry on fuel controller must have failed Replace Fuel Controller 24 Control Valve Fault Not Used 23 Position Feedback Fault Verify connectors from valve body to fuel controller are secure, not wet, and not damaged Secure LVDT Connections LVDT voltage from valve or sensing cir- cuitry on fuel controller must have failed. Replace Valve/Controller 22 Control Valve Overcur- rent Not Used 21 Control Valve Overtem- perature Verify that hot fuel is not being delivered to unit Cool Fuel System Ensure thermistor connected on fuel con- trol board Secure thermistor connec- tion to fuel control board Thermistor or sensing circuitry on fuel con- troller must have faulted. Replace Fuel Controller 20 Fuel Fault Not Used 19 Premix Injector Valve Fault Inspect Solenoid Harness at fuel controller and premix solenoid for water, damage, and secure connection Secure or Replace Solenoid Harness Replace solenoid if coil resistance is greater than TBD. Replace Solenoid Block Replace solenoid if 12Volts are measured in harness during a start sequence. Replace Solenoid Block Drive circuitry on the fuel controller must have faulted. Replace Fuel Controller 18 Pilot Injector #3 Valve Fault Inspect Solenoid cable for water, loose connections, or damage Secure or Replace Solenoid Harness Replace solenoid if coil resistance is greater than TBD. Replace Solenoid Block Replace solenoid if 12Volts are measured in harness during a start sequence. Replace Solenoid Block Drive circuitry on the fuel controller must have faulted. Replace Fuel Controller Observe Safety Precautions - Refer to Important Safety Instructions for Details Troubleshooting Guide 68 511521-002 This information is confidential and proprietary to Capstone. Neither this document nor the information contained herein shall be copied, disclosed to others, or used for any purposes other than the specific purpose for which this document was delivered.

PDF Image | Capstone SERIES 5000 FAULT CODES

PDF Search Title:

Capstone SERIES 5000 FAULT CODES

Original File Name Searched:

05_5000Faults.pdf

DIY PDF Search: Google It | Yahoo | Bing

Capstone Turbine and Microturbine: Capstone microturbines used and new surplus for sale listing More Info

Consulting and Strategy Services: Need help with Capstone Turbine, sizing systems, applications, or renewable energy strategy, we are here to assist More Info

Container Lumber Dry Kiln: Since 1991 developing and innovating dry kilns using standard shipping containers More Info

Supercritical CO2 Lumber Dry Kiln: Compact fast drying in 3 days or less for small amounts of wood and lumber drying More Info

BitCoin Mining: Bitcoin Mining and Cryptocurrency... More Info

Publications: Capstone Turbine publications for microturbine and distributed energy More Info

FileMaker Software for Renewable Energy Developing database software for the renewable energy industry More Info

CO2 Gas to Liquids On-Demand Production Cart Developing a supercritical CO2 to alcohol on-demand production system (via Nafion reverse fuel cell) More Info

Stranded Gas for low cost power Bitcoin Mining Using stranded gas for generators may provide breakthrough low power costs for cryptocurrency miners. More Info

CONTACT TEL: 608-238-6001 Email: greg@globalmicroturbine.com (Standard Web Page)