PDF Publication Title:
Text from PDF Page: 056
Capstone Turbine Corporation Model C65 Hybrid UPS User’s Manual The Under Voltage Delay establishes the time period allowed for any phase voltage to fall below the Under Voltage limit. The delay is adjustable from 0.01 up to 10 seconds in 0.01 second increments. Initial factory setting is 10 seconds. This setting can only be changed by a Capstone ASP using CRMS. 5.7.3. Over Voltage Submenu Load Output 3/4 Over Voltage 3/8 528 Vrms 10.00 Sec The Over Voltage submenu shows the line-to-line voltage trip point and associated delay time. If the RMS voltage between any phases rises above this setting the delay timer is started. If the voltage has not subsided by the end of this time span, the system will shut down. Voltage is adjustable from 528 down to nominal in 1 Volt increments. Initial factory setting is 528 Volts. Over Voltage Delay establishes the time span allowed for any phase voltage to rise above the Over Voltage limit. The delay is adjustable from 0.01 to 10 seconds in 0.01 second increments. Initial factory setting is 10 seconds. This setting can only be changed by a Capstone ASP using CRMS. 5.7.4. Frequency Submenu Load Output 3/4 Frequency 4/8 60 Hz The Frequency submenu establishes the nominal output frequency. This is adjustable from 45 to 65 in 1-Hz increments. Initial factory setting is 60 Hz. When operating in UPS Mode or High Efficiency Mode, output frequency will automatically be adjusted to maintain synchronism with input power from the Utility grid. This frequency setting, therefore, only takes precedence when the system is operating in Emergency Mode. The UPS Controller will set this frequency for all Hybrid UPS systems operating in a MultiPac, and the user cannot change this value from this Display Panel when the system is MultiPac enabled. Note that to change this value from the Display Panel, the Hybrid UPS system must be MultiPac disabled and the user must be logged in with the current password. Page 56 of 71 400027 Rev B (August 2013) Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without incurring any obligation either with respect to equipment previously sold or in the process of construction. NOTE: The Over Voltage submenu is read only, and no settings can be changed using the display panel. Protective Relay settings can only be changed by an Authorized Service Provider using CRMS.PDF Image | Capstone MicroTurbine Model C65 Hybrid UPS User's Manual
PDF Search Title:
Capstone MicroTurbine Model C65 Hybrid UPS User's ManualOriginal File Name Searched:
400027B_UM_C65_HYBRID_UPS.pdfDIY PDF Search: Google It | Yahoo | Bing
Capstone Turbine and Microturbine: Capstone microturbines used and new surplus for sale listing More Info
Consulting and Strategy Services: Need help with Capstone Turbine, sizing systems, applications, or renewable energy strategy, we are here to assist More Info
Container Lumber Dry Kiln: Since 1991 developing and innovating dry kilns using standard shipping containers More Info
Supercritical CO2 Lumber Dry Kiln: Compact fast drying in 3 days or less for small amounts of wood and lumber drying More Info
BitCoin Mining: Bitcoin Mining and Cryptocurrency... More Info
Publications: Capstone Turbine publications for microturbine and distributed energy More Info
FileMaker Software for Renewable Energy Developing database software for the renewable energy industry More Info
CO2 Gas to Liquids On-Demand Production Cart Developing a supercritical CO2 to alcohol on-demand production system (via Nafion reverse fuel cell) More Info
Stranded Gas for low cost power Bitcoin Mining Using stranded gas for generators may provide breakthrough low power costs for cryptocurrency miners. More Info
CONTACT TEL: 608-238-6001 Email: greg@globalmicroturbine.com (Standard Web Page)