Capstone MicroTurbine Model C200 User's Manual

PDF Publication Title:

Capstone MicroTurbine Model C200 User's Manual ( capstone-microturbine-model-c200-users-manual )

Previous Page View | Next Page View | Return to Search List

Text from PDF Page: 051

Capstone Turbine Corporation Model C200 User’s Manual 4.7.3. Over Voltage Submenu Stand Alone 3/4 Over Voltage 3/10 528 Vrms 10.00 Sec NOTE: The Over Voltage submenu is read only, and no settings can be changed using the display panel. Protective Relay settings can only be changed by an Authorized Service Provider using CRMS. The Over Voltage submenu shows the line-to-line voltage trip point and associated delay time. If the RMS voltage between any phases rises above this setting the delay timer is started. If the voltage has not subsided by the end of this time span, the system will shut down. Voltage is adjustable from 528 down to nominal in 1 Volt increments. Initial Factory Setting is 528 Volts. Over Voltage Delay establishes the time span allowed for any phase voltage to rise above the Over Voltage limit. The delay is adjustable from 0.01 to 10 seconds in 0.01 second increments. Initial Factory Setting is 10 seconds. This setting can only be changed by a Capstone ASP using CRMS. 4.7.4. Frequency Submenu The Frequency submenu establishes the nominal output frequency. This is adjustable from 45 to 65 in 1-Hz increments. Initial Factory Setting is 60 Hz. Note that the user must be logged in with the current password to set this frequency. 4.7.5. Under Frequency Submenu The Under Frequency submenu shows the system under frequency trip point and associated delay time. If the output frequency falls below this under frequency trip point for the set delay time, the system will shut down. The frequency is adjustable from 45 to the nominal output frequency in 0.1 Hz increments. Initial Factory Setting is 45 Hz. 400008 Rev G (October 2013) Page 51 of 64 Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without incurring any obligation either with respect to equipment previously sold or in the process of construction. Stand Alone 3/4 Frequency 4/10 60.0 Hz Stand Alone 3/4 Under Frequency 5/10 45.0 Hz 10.00 Sec NOTE: The Under Frequency submenu is read only, and no settings can be changed using the display panel. Protective Relay settings can only be changed by an Authorized Service Provider using CRMS.

PDF Image | Capstone MicroTurbine Model C200 User's Manual

PDF Search Title:

Capstone MicroTurbine Model C200 User's Manual

Original File Name Searched:

400008G_UM_C200_IND_PKG.pdf

DIY PDF Search: Google It | Yahoo | Bing

Capstone Turbine and Microturbine: Capstone microturbines used and new surplus for sale listing More Info

Consulting and Strategy Services: Need help with Capstone Turbine, sizing systems, applications, or renewable energy strategy, we are here to assist More Info

Container Lumber Dry Kiln: Since 1991 developing and innovating dry kilns using standard shipping containers More Info

Supercritical CO2 Lumber Dry Kiln: Compact fast drying in 3 days or less for small amounts of wood and lumber drying More Info

BitCoin Mining: Bitcoin Mining and Cryptocurrency... More Info

Publications: Capstone Turbine publications for microturbine and distributed energy More Info

FileMaker Software for Renewable Energy Developing database software for the renewable energy industry More Info

CO2 Gas to Liquids On-Demand Production Cart Developing a supercritical CO2 to alcohol on-demand production system (via Nafion reverse fuel cell) More Info

Stranded Gas for low cost power Bitcoin Mining Using stranded gas for generators may provide breakthrough low power costs for cryptocurrency miners. More Info

CONTACT TEL: 608-238-6001 Email: greg@globalmicroturbine.com (Standard Web Page)