Capstone Turbine Corporation • 21211 Nordhoff Street • Chatsworth • CA 91311 • USA Technical Reference: Grid Connect Operation–Capstone Models C30 and C65 3.7. Protective Relay Settings Protective relay settings establish voltage and frequency operating limits and associated fault protection for the microturbine. Voltage and frequency setpoints may be programmed as well as associated fault protection limits. These adjustments are provided to protect common loads by disabling power production during undesired transient conditions. The settings are adjustable to allow the user to narrow or restrict the operating envelope. Protective relay settings are stored in EEPROM non-volatile memory and are not subject to power interruptions. When a protective function initiates a shutdown, the following occurs: 1) Output power flow ceases within 100 msec. 2) The power output contactor is opened within 100 msec, disabling the microturbine power output from the local load. 3) Fuel flow to the microturbine stops, and 4) A warm shutdown ensues, during which control power is supplied from the microturbine generator as it slows down. The warm shutdown lasts 1 to 2 minutes before the rotor is stopped. The microturbine software supports undervoltage, overvoltage, and frequency protection limits in accordance with UL 1741. Refer to the Protective Relay Technical Reference (410033) for details. Protective Relay Settings on C30 and C65 microturbines can only be changed by an Authorized Service Provider (ASP). 3.8. VDE Settings (C65 CE only) VDE settings enable compliance with Verband der Elektrotechnik (VDE) requirements for low voltage grid connections for the European market. VDE compliance specifies fixed values for the settings, but they are adjustable via CRMS so that the same features can be used in various non-VDE applications as well. The purpose of these settings is to configure the Power Foldback on Over Frequency function. This function reduces microturbine output power at a specified ramp rate once grid frequency crosses a minimum frequency setpoint, until the frequency reaches the Over Frequency setpoint. The VDE settings include adjustment of the minimum frequency setpoint. The Over Frequency setpoint is part of the Protective Relay Settings. • CRMS: From the microturbine control panel menu, select Settings > Control Settings, set the Power Foldback on Over Freq toggle switch to ENABLE, and enter the appropriate values for Minimum Frequency and Power Reduction Gradient. CRMS Control Settings Menu Description Value Default/VDE Power Foldback on Over FreqPDF Image | Technical Reference Grid Connect Operation – Capstone Model C30 and C65
PDF Search Title:
Technical Reference Grid Connect Operation – Capstone Model C30 and C65Original File Name Searched:
410027G_TR_C30-C65_GRID_CONNECT.pdfDIY PDF Search: Google It | Yahoo | Bing
Capstone Turbine and Microturbine: Capstone microturbines used and new surplus for sale listing More Info
Consulting and Strategy Services: Need help with Capstone Turbine, sizing systems, applications, or renewable energy strategy, we are here to assist More Info
Container Lumber Dry Kiln: Since 1991 developing and innovating dry kilns using standard shipping containers More Info
Supercritical CO2 Lumber Dry Kiln: Compact fast drying in 3 days or less for small amounts of wood and lumber drying More Info
BitCoin Mining: Bitcoin Mining and Cryptocurrency... More Info
Publications: Capstone Turbine publications for microturbine and distributed energy More Info
FileMaker Software for Renewable Energy Developing database software for the renewable energy industry More Info
CO2 Gas to Liquids On-Demand Production Cart Developing a supercritical CO2 to alcohol on-demand production system (via Nafion reverse fuel cell) More Info
Stranded Gas for low cost power Bitcoin Mining Using stranded gas for generators may provide breakthrough low power costs for cryptocurrency miners. More Info
CONTACT TEL: 608-238-6001 Email: greg@globalmicroturbine.com (Standard Web Page)