PDF Publication Title:
Text from PDF Page: 008
Capstone Turbine Corporation • 21211 Nordhoff Street • Chatsworth • CA 91311 • USA Technical Reference: Capstone Model C30 Electrical Table 1. Electrical Ratings: Grid Connect (Continued) Description Single Unit MultiPac Grid Fault Current Contribution by MicroTurbine Power Required @ Start Command (per MicroTurbine) Cool Down Power (per MicroTurbine) Standby Power Grounding. Consult the Electrical Installation Technical Reference for details. Short Circuit Rating 58 Amps RMS, maximum symmetrical and asymmetrical 3.5 kW peak, 0.014 kW-Hr, 30 Seconds 2.8 kW peak, 0.147 kW-Hr, 5 minutes, typical 0.5 kW Grid must be Neutral grounded. Per UL 508C, the MicroTurbine is not short circuit rated (Note 4) N*58 Amps RMS, maximum symmetrical and asymmetrical Same as Single Unit Same as Single Unit N*0.5 kW Same as Single Unit Same as Single Unit Surge Voltage ANSI 62.45, ± 4 kV standard ± 6 kV available. A surge suppresser option must be added to achieve this requirement. Contact Capstone. Same as Single Unit Note 1: Total harmonic voltage must be less than 5% (13.85 Volts RMS line-to-neutral). Also, the high frequency ripple voltage must be less than 5.5 Volts RMS line-to-neutral at frequencies greater than 3 kHz. Note 2: The minimum typical power to the grid is 750 Watts when the Power Demand is 0 kW. For MultiPac, the typical minimum power to the grid is N*750 Watts. Note 3: Different models of MicroTurbines may be mixed within a MultiPac. The total available power is the summation of the powers available from the individual MicroTurbines. kW30HP = kW rating @ ambient conditions, of high pressure or liquid fuel Model C30 MicroTurbines kW30LP = kW rating @ ambient conditions, of low pressure Model C30 MicroTurbines N30HP = number of high pressure or liquid fuel Model C30 MicroTurbines N30LP = number of low pressure Model C30 MicroTurbines. Note 4: UL 1741 test-rated short circuit is 58 ARMS. 410000-001 Rev G (April 2004) Page 8 of 22 This information is proprietary to Capstone Turbine Corporation. Neither this document nor the information contained herein shall be copied, disclosed to others, or used for any purposes other than the specific purpose for which this document was delivered. Capstone reserves the right to change or modify without notice, the design, the equipment ratings, and/or the contents of this document without incurring any obligation either with respect to equipment previously sold or in the process of construction.PDF Image | TECH REF 30 ELEC
PDF Search Title:
TECH REF 30 ELECOriginal File Name Searched:
410000_C30_Electrical.pdfDIY PDF Search: Google It | Yahoo | Bing
Capstone Turbine and Microturbine: Capstone microturbines used and new surplus for sale listing More Info
Consulting and Strategy Services: Need help with Capstone Turbine, sizing systems, applications, or renewable energy strategy, we are here to assist More Info
Container Lumber Dry Kiln: Since 1991 developing and innovating dry kilns using standard shipping containers More Info
Supercritical CO2 Lumber Dry Kiln: Compact fast drying in 3 days or less for small amounts of wood and lumber drying More Info
BitCoin Mining: Bitcoin Mining and Cryptocurrency... More Info
Publications: Capstone Turbine publications for microturbine and distributed energy More Info
FileMaker Software for Renewable Energy Developing database software for the renewable energy industry More Info
CO2 Gas to Liquids On-Demand Production Cart Developing a supercritical CO2 to alcohol on-demand production system (via Nafion reverse fuel cell) More Info
Stranded Gas for low cost power Bitcoin Mining Using stranded gas for generators may provide breakthrough low power costs for cryptocurrency miners. More Info
CONTACT TEL: 608-238-6001 Email: greg@globalmicroturbine.com (Standard Web Page)