C800 Capstone Turbine Available

global energy capstone turbine c800 surplus for sale

C800 Capstone Turbine Dual Mode Microturbine For Sale (posted September 12, 2020)

New surplus. Dual mode.

Model 800S-FD4-BE00. MFG 2016.

Applications: Primary or backup power. Greenhouse or grow operations. Hurricane power. Forest fire backup power when the grid goes down. Waste heat can be used directly for drying hemp, firewood, and lumber in a container kiln. Cogeneration to produce both heat, hot airflow, and power for drying operations.

Output: 480V 3 Phase 50/60 hz selectable. 760 kW nominal power output.

Dual Mode: Can be used with the grid, or completely off-grid in a stand alone configuration. Grid Connect (480V 3 phase) and Stand Alone (400-480V 3 phase). KVA 760 Grid Connect / KVA 832-1000 Stand alone.

MFG: UL listed. Made in USA. Insulation class N. NEMA 3R containerized system.

Fuel Input: Low pressure natural gas with H2S<5 ppmv. 825 btu/scf to 1276 btu/scf heat value.

Natural Gas Pressure: Minimum operating pressure: 0.25 psig Maximum operating pressure: 5.0 psig operating pressure.

Currently first owner is a large company that never installed the unit.

Recertification (warranty) may available from Capstone (will need to contract through Capstone directly if interested).

For pricing and information:

TEL (USA +1): 608-238-6001

Contact Email: greg@globalmicroturbine.com

global energy capstone turbine c800 surplus for sale
global energy capstone turbine c800 surplus for sale

Low pressure natural gas with H2S<5 ppmv. 825 btu/scf to 1276 btu/scf heat value. .25 psig to 5 psig operating pressure. Recertification (warranty) may be available from Capstone.

global energy capstone turbine c800 surplus for sale
global energy capstone turbine c800 surplus for sale

User Manual C1000: https://globalmicroturbine.com/wp-content/uploads/2019/03/c1000manual.pdf

Rating: 800 kW
Electrical Efficiency LHV: 33%
Combined Heat And Power Efficiency:: Up to 90%
Voltage (dual mode): 400-480 VAC
Frequency: 50/60 Hz, Grid Connect
60 Hz,
Electrical Service: 3-Phase, 4-Wire Wye

Dimensions (meters): 2.4 x 9.1 x 2.9 m (96 x 360 x 114 in)

Dual Mode Weight: 17917 kg (39,500 lbs)

Compatible Fuels: Natural Gas (low pressure)

EGT (Exhaust Gas Flow): 5.3 kg/s (11.7 lbm/s) 280°C (535°F) 5,680 MJ/hr (5,400,000 BTU/hr)

Drying Hemp in a Container Kiln Dryer with a Capstone Turbine C800:

Using the Capstone Turbine to dry hemp in combination with a conveyor dryer or drum dryer, expect the following throughput based on 970 btu to evaporate 1 pound of water. The Capstone Turbine exhaust can be mixed with dry outside air to direct heat a hemp dryer. Alternatively, put output into a stainless steel pipe and then use fans to circulate and heat air in dyer. This is in the true sense cogeneration (produce both usable heat and power at the same time). The power can be used to run fans, or exported to the grid for utility buyback (typically more hassle and low buyback rate than it’s worth). Because this is dual mode, you can trailer mount this module along with a trailer mounted drum dryer or conveyor dryer module for portable drying (bring to the farm fields directly). You will need a propane tank trailer and associated interconnection equipment to fuel system. Alternatively, you can truck in the hemp flower from the fields in a hub-spoke system.

C800 Net Heat Rate: 10,300 BTU/kWh x 800 kW power = 8,240,000 btu/hr

8,240,000 btu/hr / 970 btu/lb/water = 8,494.85 lbs water

Heat Available for Evaporation: 8,240,000 btu/hr available / 970 btu/lb/water evaporation = 8,494.85 lbs water evaporated per hour under standard conditions.

Hemp Production Per Acre Variables: One acre of hemp flower drying to 10 percent moisture content (i.e. removing 90 percent water weight):

500 lbs per acre hemp flower harvest: @ 90 percent evaporate = 450 lbs –> 8,494.85 lbs water (c800) / 450 lbs = 18 acres per hour

1,000 lbs per acre hemp flower harvest: @ 90 percent evaporate 8,494.85 lbs water (c800) / 900 lbs = 9 acres

1,500 lbs per acre hemp flower harvest: @ 90 percent evaporate 8,494.85 lbs water (c800) / 1,350 lbs = 6 acres per hour

2,000 lbs per acre hemp flower harvest: @ 90 percent evaporate 8,494.85 lbs water (c800) / 1,800 lbs = 4 acres per hour

 

 